Compressor cycling on and off every 3 minutes. Possible high head pressure or refrigerant issue. Customer worried about overheating and total failure.
Marcus Webb
Temperature probe on produce cool room reading 1.8°C below actual. May be faulty or calibration drift.
Tested probe against calibrated reference. Confirmed 1.8°C drift. Replaced with new NTC probe. Recalibrated controller. Now reading within 0.1°C of reference.