Coldchain
Dashboard
CRJ-2608-004
Donehigh

FreshChilled Depot

15 Distribution Dr, Wetherill Park NSW 2164

Contact

Tony Rossetti

(02) 9725 4300

Reported by

Tony Rossetti

Engineer

Marcus Webb

0445 678 901

Created

Mon 10 Aug, 7:00 AM

Started

Mon 10 Aug, 8:00 AM

Completed

Mon 10 Aug, 2:00 PM

Site note: Gate code: 4782. After hours call Tony mobile 0412 654 321.

Fault Description

Evaporator coil fully iced up on 40-pallet cool room. Auto-defrost cycle appears to have failed. Room temperature risen to 8°C.

Completion Notes

Manual defrost performed (4 hours). Defrost timer motor seized — replaced. Checked defrost heater elements — all OK. Two full defrost cycles confirmed working. Room back to -18°C setpoint.

Actions

Parts Used

PartPart No.Qty
Defrost Timer Motor 220VDTM-220V-601

Notes

No notes yet.