Coldchain
Dashboard
CRJ-2608-001
Donecritical

Woolworths Parramatta

159-175 Church St, Parramatta NSW 2150

Contact

Kerry Walsh

(02) 9891 3300

Reported by

Kerry Walsh

Engineer

Dave Mitchell

0412 345 678

Created

Wed 12 Aug, 8:15 AM

Started

Wed 12 Aug, 9:00 AM

Completed

Wed 12 Aug, 11:30 AM

Fault Description

Refrigerant leak detected in bakery section cool room. Faint gas smell. Product temperatures rising rapidly.

Completion Notes

Located leak at brazed joint on suction line. Repaired and pressure-tested to 450 kPa. Recharged with 2.5 kg R404a. System back to setpoint. Advised manager to ventilate for 30 minutes.

Actions

Parts Used

PartPart No.Qty
R404a Refrigerant (11.3kg cylinder)R404A-11.31

Notes

No notes yet.